CAL3:INIT:CURR 5.0
// set power-on initial current of channel 3 to 5.0 A.
CAL3:INIT:CURR?
// confirm power-on initial current setting.
CAL3:INIT:VOLT 10.0
// set power-on initial voltage of channel 3 to 10.0 VDC.
CAL3:INIT:VOLT?
// confirm power-on initial voltage setting.
CAL3:INIT:VOLT:PROT 11.0
// set power-on initial overvoltage protection of channel 3 to 11.0
//VDC.
CAL3:INIT:VOLT:PROT?
// confirm power-on initial overvoltage protection setting.
// cycle power to the unit.
// note voltage is initialized to 2.0 VDC via front panel.
SOUR1:CURR?
// confirm power-on initial current setting of channel 1.
SOUR1:VOLT?
// confirm power-on initial voltage setting of channel 1.
SOUR1:VOLT:PROT?
// confirm power-on initial overvoltage protection setting of
//channel 1.
SOUR2:CURR?
// confirm power-on initial current setting of channel 2.
SOUR2:VOLT?
// confirm power-on initial voltage setting of channel 2.
SOUR2:VOLT:PROT?
// confirm power-on initial overvoltage protection setting of
//channel 2.
SOUR3:CURR?
// confirm power-on initial current setting of channel 3.
SOUR3:VOLT?
// confirm power-on initial voltage setting of channel 3.
SOUR3:VOLT:PROT?
// confirm power-on initial overvoltage protection setting of
//channel 3.
Summary of Contents for Sorensen Asterion DC ASM
Page 1: ...M330517 01 Rev C Asterion DC Multioutput Series Programming Manual...
Page 6: ...Asterion DC Multioutput Series Programming Manual M330517 01 Rev C v SAFETY SYMBOLS...
Page 145: ...Asterion DC Multioutput Series Programming Manual 13 128 M330517 01 Rev C CAL n LOCK...
Page 162: ...M330461 01 Rev C 14 145...