background image

DP-660 

Industrial Power Supply 

 

User’s Manual 

 
 
 
 
 
 
 
 

Introductions ..................................................................................................................1 

1.0 Input 

Specifications ...............................................................................1 

2.0 Output 

Specifications.............................................................................1 

3.0 General 

Features ....................................................................................2 

4.0 Environment 

specifications....................................................................2 

5.0 International 

standards ...........................................................................3 

6.0 Mechanical 

Specification.......................................................................4 

 

Summary of Contents for DP-660

Page 1: ...al Power Supply User s Manual Introductions 1 1 0 Input Specifications 1 2 0 Output Specifications 1 3 0 General Features 2 4 0 Environment specifications 2 5 0 International standards 3 6 0 Mechanical Specification 4 ...

Page 2: ... 25deg C 2 0 Output Specifications 2 1 Load range Output Min load Rated load Peak load Voltage accuracy 24V 0A 2 5A 6A 23 76V to 24 24V 5V 0a 0 5A 4 75V to 5 25V At Factory all outputs in 60 rated load conditions the 24V output is set to between 23 76V and 24 24V and 5V is checked to be within the specified voltage accuracy range Peak load can test for 10 sec Typical when other output at rated loa...

Page 3: ...put and rated load which is measured from the end of the last charging pulse to when the main output drops down to 95 output voltage 3 3 Protection For some reason the power supply fails to control itself the build in over voltage protection circuit will shut down the outputs to prevent damaging external circuits The trip point is around 26V to 31V The power supply will go into latch off mode agai...

Page 4: ...frame testing Board only Internal PCB model No SNP 9069 5 1 Safety standards Designed to meet the following standards UL 1950 D3 CSA 22 2 No 234 VDE EN 60 950 5 2 EMI standards Designed to meet the following conducted limits FCC docket 20780 curve B VFG 243 3 ...

Page 5: ...ion Dimensions 44mm W x 150mm H x 122mm D 6 1 G N D G N D 5 O u t p u t D C 2 4 V 2 5 A D C 5 V 0 5 A DP 660 I n d u s t r i a l P o w e r S u p p l y N L N C F G 8 5 2 6 4 V A C I n p u t 5 0 6 0 H z 1 1 5 V 2 A 2 3 0 V 1 A 4 ...

Page 6: ...1 AC inputs connector Pitch 5 08mm screw terminal block Wire range 12AWG 22AWG 2 5mm Pin Assignments No connection Frame Ground AC Input N L N C F G 6 2 2 DC output connector Pitch 5 08mm screw terminal block Wire range 12AWG 22AWG 2 5mm Pin Assignments 5V Loading 24V Loading 24V GND GND 5V 5 ...

Reviews: