www.accuenergy.com
V: 1.10 Revised: January 2020
92
AXM-WEB2 for Acuvim II Series Power Meter
Select the Post Channel 3 tab to configure the settings for post to a second server.
Post Channel 3 Enable:
Enable the Post Channel 3 in order to configure the settings need
-
ed to post data via the HTTP(S)/FTP post functions
Post Method:
Select the method for posting the files, the user can choose HTTP/HTTPS or
FTP
Post Name Fixed:
This configuration needs to be enabled in order for user to control the
name of the file that will be posted. Otherwise file name will be based on the Log File Name
Format configuration from the Data Log settings
Post File Name:
User can enter a name for the file that will be posted as if Post Name Fixed
is enabled
If the HTTP/HTTPs post method is selected:
HTTP/HTTPS URL:
Enter the URL for the HTTP/HTTPS server. The URL needs to begin with
the prefix http:// or (https://)
HTTP/HTTPS Port:
Enter the port number the server will be listening on
HTTP/HTTPS Meter ID:
Enter a name or description for the meter to be identified on the
server
If the FTP post method is selected:
FTP URL:
Enter the URL for the FTP server. The URL needs to begin with the prefix ftp://
FTP Port:
Enter the port number the server will be listening on
FTP Username:
Enter the username required to log into the FTP server
FTP Password:
Enter the password required to log into the FTP server
NOTE:
The "TEST Post Channel 3" button should only be utilized after clicking the 'Save'
button otherwise a fail response will be observed. If the test post fails users can view the
test post details by clicking on the 'Details' option from the test post screen.
Click 'Save' after changing any settings. Users will be prompted to reboot the AXM-WEB2
immediately or later. If later is chosen the AXM-WEB2 must be rebooted from the 'Manage-
ment' page in order for the settings to take effect.