AXM-WEB2 for Acuvim II Series Power Meter
CT1: Enter the rated input of the current transformer that is used with the meter. Possi-
ble ranges for the CT1 are from 1 to 50000A.
The default settings for CT1 are dependent on the current input type of the Acuvim II
meter. The following table displays the default CT1 values for the different Current in-
put options.
Acuvim II Current Input
Default CT1 Value
1A
1
5A
5
333mV
1
RCT
1000
80mA/100mA/200mA
1
CT2:
Select the rated output of the current transformer from the drop down list. By de-
fault this setting is already configured.
NOTE: CT2 is configurable only for 5A and mA current inputs, 5A can be either 5A or 1A
and mA can be either 80mA, 100mA or 200mA.