Chapter 10: Web Interface Readings and Parameter Settings
10.6.8 Config Management
The AXM-WEB2 module has a configuration management page that allows users to
save all web settings with the exception of a certain settings into a configuration file.
This is useful if users have more than one meter that needs to be programmed with
the same settings, and eliminates any error when trying to configure another WEB2
module.
The following settings are saved in the configuration file:
• All Meter settings (General, IO, Alarm, Custom Read, Waveform)
• Network settings (Only DNS1, DNS2, Modbus TCP Port, HTTP Proxy)
• All Email settings
• All Time/Date settings
• All Data Log settings
• All Post Channel settings
• All BACnet settings
• All SNMP settings
• All DNP settings (Point configuration will also be applied)
• All IEC61850 settings (CID file will also be applied)
• Management settings (the View and Admin Access Level passwords, SSH, and
Debug Configuration)
The settings that are not included or effected by the Config Management file is:
• Most Network settings (RSTP, DHCP, IP, Submask, Gateway, HTTP Port for both
Ethernet 1 and 2. All WiFi settings, Fast Read Mode, HTTP enable, and HTTPS
port are not changed)
• IPv6
• AcuCloud
• Remote Access