www.accuenergy.com
V: 1.10 Revised: January 2020
72
AXM-WEB2 for Acuvim II Series Power Meter
If user are using external I/O modules, the waveform capture can be triggered by the Digital
Inputs Status. The DI can trigger the waveform by the following:
•
From Status Off to On
•
From Status On to Off
• Any Change
The DI triggering can be disabled is users do not require it to trigger the waveform capture.
10.6.2 Communications
The communication setting web page will allow the user to configure settings related to
the Ethernet networks and the Wireless network. The functions and protocols that the AXM-
WEB2 module supports can be configured by selecting the corresponding tab such as Emails,
Time/Date , Datalog, AcuCloud Post for communicating with the AcuCloud software, BAC-
net-IP, SNMP, IEC61850, and DNP3.
Network
The first page the user will see after selecting the Communications option under the Set-
tings tab is the Network page. The network settings allow users to configure all network
related settings including both Ethernet 1 and Ethernet 2 as well as WiFi.
RSTP Protocol
The AXM-WEB2 supports the RSTP protocol where users can daisy chain the Ethernet ports
on the AXM-WEB2 module to a network switch.
Users can configure the meters IP manually or by setting the DHCP set as Auto.