www.accuenergy.com
V: 1.10 Revised: January 2020
28
AXM-WEB2 for Acuvim II Series Power Meter
Fun
Byte
count
Data1
hi
Data1
lo
Data2
hi
Data2
lo
Data3
hi
Data3
lo
Data4
hi
Data4
lo
Data5
hi
Data5
lo
Data6
hi
Data6
lo
03H
0CH
07H
D6H
00H
0CH 00H 12H 00H 0EH 00H 0FH 00H 14H
4) Control Relay (Function Code05)
Function Code 5
Query
This function code enables the control of a single relay output in the Acuvim II series me-
ter. Any relay output in the Acuvim II series meter can be controlled on or off starting at
0000H.
Sending the data 'FF00H' will set they relay output on and sending '0000H' will turn it off;
all other values are illegal and will not affect they relay output status.
The example below is a request to a Acuvim II series meter to turn on relay output 1.
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi
Length lo
Unit
identifier
00H
00H
00H
00H
00H
06H
01H
Fun
Data start
reg hi
Data start
reg lo
Data #of
reg hi
Data #of
reg lo
05H
00H
00H
FFH
00H
Response
The normal response to the command request is to retransmit the message as received
after the relay output status has been altered.
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi
Length lo
Unit
identifier
00H
00H
00H
00H
00H
06H
01H
Fun
Data start
reg hi
Data start
reg lo
Value hi
Value lo
05H
00H
00H
FFH
00H