AXM-WEB2 for Acuvim II Series Power Meter
Unsolicited response trigger Condition(Num of class # events): Enter the number of events
for each class to setup the trigger point. The unsolicited response will be triggered once the
number the class events reaches the configured triggering number. The range is from 0-255.
Unsolicited response trigger Condition(Hold time after class # events): Enter the threshold
holding time for each class, the unsolicited response will be triggered once the event holding
time is longer or equal to the threshold time. The range is from 0-86400000 milliseconds.
Support for broadcast functionality: In DNP there three broadcasting addresses that are sup-
ported. Enabling this setting would allow the module to respond to requests (from the client)
sending them to the broadcasting addresses.
DNP3 Point Configuration
Users can assign certain parameters to either class 1, class 2 or class 3.
The scale factor is a multiplier that can be applied to a certain parameter when viewing the
readings.
An offset can be applied to the reading.
The dead band can be set for each parameter, where if the value of the parameter exceeds the
dead band value a DNP event will occur.