AXM-WEB2 for Acuvim II Series Power Meter
AXM-IO2-1/2
The AXM-IO2 module supports 4 Digital Input channels, 2 Digital Output channels, and 2
Analog Output channels.
•
Digital Input - Can be configured as either digital status or pulse counter.
•
DI Pulse Constant - If the DI is configured as pulse counter, then the DI pulse constant
will represent how many pulses equals one count, i.e pulse constant is 2 that means
that every 2 pulses the inputs reads the counter is increased by 1.
•
Digital Output - Can be configured for Pulse or Alarm mode.
• DO 1 Output - Users can select the type of energy pulse outputted from DO Channel 1
• DO 2 Output - Users can select the type of energy pulse outputted from DO Channel 2
• There are 4 types of energy that can be used for Energy Pulse Output:
1. System Import Active Energy
2. System Export Active Energy
3. System Import Reactive Energy
4. System Export Reactive Energy
•
Pulse Width - Users can configure the Energy pulse width, the range is from 20-1000ms
• DO Active Energy Pulse Constant - Select the Pulse Constant for Active Energy Pulse,
the range is from 1-60000
• DO Reactive Energy Pulse Constant - Select the Pulse Constant for Reactive Energy
Pulse, the range is from 1-60000