www.accuenergy.com
V: 1.10 Revised: January 2020
49
Chapter 10: Web Interface Readings and Parameter Settings
10.4.6 Waveform Log
The waveform log is available only on Acuvim IIW models of the Acuvim II series meter.
This meter supports a waveform capture function that allows users to capture and record
10 cycles before and after the triggering point whether it be a voltage sag, swell, or over
current. The waveform log on the web interface allows users to view these waveforms
whenever a power quality event has occurred. The log displays is a table that includes the
waveform files, the time the waveform is updated at, and the size of the file. The wave
-
form file name includes the timestamp when the event occurred as well as the parameter
name/event name that triggered the power quality event.