www.accuenergy.com
V: 1.10 Revised: January 2020
98
AXM-WEB2 for Acuvim II Series Power Meter
SNMP
The AXM-WEB2 module supports the Simple Network Management Protocol(SNMP) protocol
for reporting the metering data to the management station. The AXM-WEB2 uses a public com-
munity string for read-only access. By default the module will communicate using SNMP port
161. The AXM-WEB2 also supports 'traps' to send unsolicited messages to up to four manage-
ment stations.
The settings for the SNMP protocol can be found by clicking on the 'Settings' tab and selecting
'Communications'. From the communications page select the 'SNMP' tab to access the settings
to configure the AXM-WEB2 for communication with a SNMP management station.
SNMP Enable:
Select 'Enable' to enable the function and to further configure the settings relat
-
ed to the SNMP protocol.
SNMP Port: By default the SNMP Port is configured to 161. The SNMP Port can be any value
from ranging from 16100 to 16199.
Read Only Community: By default the community string is Public, this configuration is similar
to a password which allows only authorized users to access the meters data.
Trap Enable:
Select 'Enable' so that the meter will send a message to the management station
when an event is triggered. The event could be a change in Digital Input Status. The notification
can then be sent to up to 4 stations.
Trap Target 1: Enter the IP address and port number of station number 1 that should be noti-
fied when there is an event.
Trap Target 2: Enter the IP address and port number of station number 2 that should be noti-
fied when there is an event.
Trap Target 3: Enter the IP address and port number of station number 3 that should be noti-
fied when there is an event.
Trap Target 4: Enter the IP address and port number of station number 4 that should be noti-
fied when there is an event.
Report Buffer Size: Enter the size of the buffer for the amount of notifications will be stored
before being sent to the management station. A maximum of 30 notifications can be stored.
Report Hold Time: Enter the time in seconds for how long the notification will be in queue
before it gets sent to the management station. By default, this setting is configured to 0 so the
notification will be sent immediately after an event occurs. This setting could be configured
from 0-30 seconds.