Configuration
91
Name/function
Explanation
Exit Mode,
cont.
Disarming the partition
The user unlocks the door and therefore activates the lock switch contact.
The "Lock Set" zone is opened.
The alarm panel saves the activation of the "Lock Set" zone in the log book.
The original "Final Door" zone which was converted into a "Normal Alarm" zone is
switched back into a "Final Door" zone.
The entry time starts when the door is opened.
The entry tone sounding at this point is different from a normal entry tone.
If the user locks the door again without starting the entry time, the alarm panel re-
mains armed and the "Final Door" zone is converted again into a "Normal Alarm"
zone. The alarm panel stops the warning tone.
To comply with BS8243, "After Entry" must be set to "Never" in order to prevent
confirmation.
Exit Terminate
Arming the partition
The user must first start the arming sequence. Then the user ends the arming
process after existing the monitoring area.
The user can start the arming sequence using the user code, proximity keyfob or
remote control. (Note: arming with remote control must not be set to "Instant", In-
staller Mode->System->User Access->Remote Inst. Set).
The user ends arming by activating a zone with type "Exit Terminate" (see expla-
nation of zone types).
Note that the exit time is unlimited with this option, i.e. the alarm panel waits until
it receives the signal to end the arming process before it arms. The alarm panel
emits the exit tone during this time. The alarm panel saves the start time of arm-
ing (and not the arming itself) in the log book. The partition is armed after the set-
tle time has expired.
Disarming the partition
The user can use the remote control. The user can also open the door. The "Final
Door" zone at this door starts the entry time. During entry time the user must dis-
arm the partition using the user code or proximity keyfob at the alarm panel or
control device. (The last method is not compliant with BS8243 clause 6.4.)
As SA (partition) 1
This option is available for partitions 2, 3 and 4. If this option is selected, the alarm
panel uses the same type as for partition 1.
Settle time [s]
This option only appears for modes "Final Door Set", "Lock Set" and "Exit Termi-
nate".
Use this option to define a time delay so that detectors can settle before the partition
is armed. This may be necessary if detectors have triggered, send an alarm signal
and have still not been reset. During this time the alarm panel ignores alarm signals
from detectors and sirens are not triggered. Enter the time in seconds as a 2-digit
number: 01
–30. The factory default for the settle time is 15 s. In this time the wire-
less PIRs located at the exit which have triggered can settle and be reset.
Summary of Contents for SECVEST FUAA50 Series
Page 12: ...Device overview 12 International key assignment...
Page 39: ...Configuration 39 Communication...
Page 46: ...Configuration 46 Components Teach in via web interface...
Page 74: ...Configuration 74 Outputs...
Page 85: ...Configuration 85 1 Select menu item Type...
Page 94: ...Configuration 94...
Page 111: ...Configuration 111 System...
Page 148: ...Configuration 148 Communication Network...
Page 157: ...Configuration 157 ARC reporting...
Page 159: ...Configuration 159...
Page 177: ...Configuration 177 Voice dialler S W 3 00 05...
Page 185: ...Configuration 185...
Page 216: ...Configuration 216...
Page 229: ...Configuration 229 Log S W v2 01 08...
Page 278: ...Appendix 278...
Page 326: ......