Configuration
90
Name/function
Explanation
Exit Mode,
cont.
Final Door Set
Use this option to complete arming of a partition by closing the last exit door. This
door has a detector with zone type "Final Door". When the door is closed, the par-
tition is armed once the settle time has expired.
Note that the exit time for this option is unlimited, i.e. when the zone is closed
(closed door) the alarm panel waits until this zone is opened and then closed
again before arming.
The alarm panel saves the start time of arming (and not the arming itself) in the
log book.
Do not attempt to use a PIR zone as a "Final Door" for a partition. PIR wireless
detectors has a "lock" time period after each arming, in order to save battery
power. If a partition is armed (or internally armed), a PIR detector may still be
locked. During this time it cannot send signals to complete the arming process.
Instant Set
The partition is armed immediately without any acoustic warning tone. If the parti-
tion has been armed, an acoustic confirmation sounds.
Note: This option does not comply with BS8243:2010.
Silent Set
The partition is armed after the exit time has expired. Under "Exit time" select the
corresponding time. However, no warning tone sounds during this time. If the par-
tition has been armed, an acoustic confirmation sounds. The alarm panel saves
the start time in the log book.
During entry time the acoustic warning tone can be heard.
Note: This option does not comply with BS8243:2010.
Lock Set
The "Lock Set" mode affects both arming and disarming of the partition.
For this mode, a detector with zone type "Lock Set" and a detector with zone type
"Final Door" must be assigned at the last exit door. The detector with zone type
"Lock Set" is operated with a lock switch contact on a suitable lock.
Arming the partition
The user must first start the arming sequence using the user code, proximity
keyfob or remote control.
The alarm panel then sounds the exit tone and saves the start time in the log
book.
If the "Final Door" zone is open, the alarm panel emits a continuous exit tone.
The exit tone sounds until the user:
a) closes the last exit door and then
b) locks the door and therefore activates the lock switch contact.
After the lock switch contact is activated, the partition is armed once the settle
time has expired. The "Final Door" zone is also converted into a "Normal Alarm"
zone.
The alarm panel saves the activation of the "Lock Set" zone in the log book.
Summary of Contents for SECVEST FUAA50 Series
Page 12: ...Device overview 12 International key assignment...
Page 39: ...Configuration 39 Communication...
Page 46: ...Configuration 46 Components Teach in via web interface...
Page 74: ...Configuration 74 Outputs...
Page 85: ...Configuration 85 1 Select menu item Type...
Page 94: ...Configuration 94...
Page 111: ...Configuration 111 System...
Page 148: ...Configuration 148 Communication Network...
Page 157: ...Configuration 157 ARC reporting...
Page 159: ...Configuration 159...
Page 177: ...Configuration 177 Voice dialler S W 3 00 05...
Page 185: ...Configuration 185...
Page 216: ...Configuration 216...
Page 229: ...Configuration 229 Log S W v2 01 08...
Page 278: ...Appendix 278...
Page 326: ......