SAPPHIRE COMPACT FIXED FIRE SUPPRESSION SYSTEM 

LOCAL ALARM UNITS

2019-SEP-30    REV. 00    PAGE 1

Burlingham House, Hewett Road, Gapton Hall Industrial Estate, Great Yarmouth, NR31 0NN 

|

  +44 (0)1 493 417600

www.hygood.com 

|

  © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were  

current as of document revision date and are subject to change without notice. 

|

  Part No. HY-2019023

PRINCIPLES OF OPERATION 

HYGOOD® SAPPHIRE® COMPACT Local Alarm Units 

are intended to enable system installers to offer full and 

complete monitoring of the health and status of HYGOOD 

SAPPHIRE COMPACT Fixed Fire Suppression System 

installations.
They offer alarm indications comprising of both an initial 

combined 30 second sounder and flashing beacon, followed 

by a continuous flashing beacon.
The alarm units come in three colour options for the beacon. 

Each colour has two base unit options that are activated 

by either 

Normally Open

 (N/O) or 

Normally Closed

 (N/C) 

switches. The three colour options are orange, blue, and 

red.

Alarm unit

Description
Orange - low pressure alarm

The low pressure alarm indicates when SAPPHIRE COMPACT pressure is below the lowest 

normal system operating pressure. This occurs at the lowest system operating temperature.
The low pressure alarm triggers through a pressure gauge with a switch contact. Use a 

higher pressure switch contact if two fitted.

Blue - system discharged alarm

The system discharged alarm indicates when the SAPPHIRE COMPACT system discharged.
The system discharged alarm triggers through a pressure gauge with a switch contact, 

pressure switch, or integrated control valve activation switch. Use a lower pressure switch 

contact if two fitted.

Red - system isolated alarm

The system isolated alarm indicates when the SAPPHIRE COMPACT system valve is closed.
The system isolated alarm triggers through an integrated ball valve position switch, where 

available.

Part No.

Description

Notes

309150001

Low pressure alarm with orange lens

For use with 

Normally Open 

contacts 

(N/O) when conditions are good. 

(Contacts close on alarm).

309150002

System discharged alarm with blue lens

309150003

System isolated alarm with red lens

309150004

Low pressure alarm with orange lens

For use with 

Normally Closed

 contacts 

(N/C) when conditions are good. 

(Contacts open on alarm).

309150005

System discharged alarm with blue lens

309150006

System isolated alarm with red lens

Summary of Contents for SAPPHIRE COMPACT 309150001

Page 1: ... indicates when SAPPHIRE COMPACT pressure is below the lowest normal system operating pressure This occurs at the lowest system operating temperature The low pressure alarm triggers through a pressure gauge with a switch contact Use a higher pressure switch contact if two fitted Blue system discharged alarm The system discharged alarm indicates when the SAPPHIRE COMPACT system discharged The syste...

Page 2: ...150004 N C contact required 309150005 N C contact required 309150006 N C contact required Lens material Polycarbonate Note Polarity sensitive terminals FIXING THE ALARM UNIT FIXING HOLE DIA 4 mm FIXING HOLE DIA 4 mm Front FIXING HOLE DIA 4 mm FIXING HOLE DIA 4 mm Reverse FIGURE 2 E001097 1 Fix the alarm unit using the fixing hole locations in Figure 2 2 Use the rawl plugs and screws provided if ap...

Page 3: ...key switch attached to the lens ORANGE WIRE GREEN WIRE Not connected Connected FIGURE 5 E001101 1 Using the key supplied turn the key switch 90 from 12 o clock to 3 o clock see Figure 6 in order to set the alarm unit 2 To service isolate the alarm unit by turning the key switch 90 3 o clock to 12 o clock 3 To reset the alarm unit cycle the key switch from 3 o clock to 12 o clock and then back to 3...

Page 4: ...ormally Closed contact 309150005 Normally Closed contact 309150006 Normally Closed contact 1 Always connect primary inputs to SW1 and Common on Alarm Unit 1 2 If using a pressure gauge with two switch contacts connect secondary inputs to SW2 and Common on Alarm Unit 1 3 If required connect SW2 and Common outputs to SW1 and Common inputs on Alarm Unit 2 4 For Alarm Units 1 and 2 if fitted or requir...

Page 5: ...ts M10x1 N C contacts at 15 bar nominal charge pressure 302150011 liquid filled variant for environments subject to vibration Signal generator pressure switch 4 0 8 0 bar switch point M10 x 1 3 wire black red brown optional N O black and brown or N C black and red when pressure good 302150008 DLP valve one outlet for detection tube one outlet with G1 8 in plug with internal ball valve and sensor o...

Page 6: ...ESSION SYSTEM LOCAL ALARM UNITS PAGE 6 REV 00 2019 SEP 30 NOTES 3M and Novec are trademarks of 3M Company HYGOOD SAPPHIRE and the product names in this material are marks and or registered marks Unauthorised use is strictly prohibited ...

Reviews: