Table 31: Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Synch source
0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
17=IEC60870-5-10-3
1=SNTP
Time synchronization
source
PTP domain ID
0...255
1
0
The domain is identi-
fied by an integer, the
domainNumber, in the
range of 0 to 255.
PTP priority 1
0...255
1
128
PTP priority 1, in the
range of 0 to 255.
PTP priority 2
0...255
1
128
PTP priority 2, in the
range of 0 to 255.
PTP announce
mode
1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588
PTP announce frame
mode
Table 32: Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Date
0
Date
Time
0
Time
Local time offset
-840...840
min
1
0
Local time offset in mi-
nutes
Table 33: Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
IP SNTP primary
10.58.125.165
IP address for SNTP primary
server
IP SNTP secondary
192.168.2.165
IP address for SNTP secon-
dary server
Table 34: Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
DST in use
0=False
1=True
1=True
DST in use setting
DST on time
(hours)
0...23
h
2
Daylight saving time on, time
(hh)
DST on time (mi-
nutes)
0...59
min
0
Daylight saving time on, time
(mm)
DST on date (day)
1...31
1
Daylight saving time on, date
(dd:mm)
DST on date
(month)
1=January
2=February
3=March
5=May
Daylight saving time on, date
(dd:mm)
Table continues on the next page
Basic functions
1MRS758755 C
72
REC615 & RER615
Technical Manual