Name
Type
Values (Range)
Unit
Description
I_RANGE_RES
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Residual current
Amplitude range
Max demand Io
FLOAT32
0.00...40.00
xIn
Maximum de-
mand for residu-
al current
Min demand Io
FLOAT32
0.00...40.00
xIn
Minimum de-
mand for residu-
al current
Time max de-
mand Io
Timestamp
Time of maxi-
mum demand re-
sidual current
Time min de-
mand Io
Timestamp
Time of mini-
mum demand re-
sidual current
8.1.6.6
Technical data
Table 605: RESCMMXU Technical data
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±0.5 % or ±0.002 × I
n
(at currents in the range of 0.01...4.00 × I
n
)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
8.1.6.7
Technical revision history
Table 606: RESCMMXU Technical revision history
Technical revision
Change
B
-
C
Residual current angle and demand value
added to Monitored data view. Recorded da-
ta added for minimum and maximum values
with timestamps.
D
Monitored data Min demand Io maximum val-
ue range (RESCMSTA2.MinAmps.maxVal.f ) is
corrected to 40.00.
E
Internal improvement
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual