3.1.6
Binary input settings
Table 12: Binary input settings
Parameter
Values (Range)
Unit
Step
Default
Description
Threshold voltage
16...176
Vdc
2
16
Binary input
threshold voltage
Input osc. level
2...50
events/s
1
30
Binary input oscil-
lation suppression
threshold
Input osc. hyst
2...50
events/s
1
10
Binary input oscil-
lation suppression
hysteresis
Adjust the binary input threshold voltage correctly. The threshold voltage
should be comparable to the nominal value instead of the default
minimum value. The factory default is 16 V to ensure the binary inputs’
operation regardless of the auxiliary voltage used (24, 48, 60, 110, 125,
220 or 250 V DC). However, the default value is not optimal for the
higher auxiliary voltages. The binary input threshold voltage should be
set as high as possible to prevent any inadvertent activation of the binary
inputs due to possible external disturbances. At the same time, the
threshold should be set so that the correct operation is not jeopardized
in case of undervoltage of the auxiliary voltage.
3.1.7
Binary signals in card location Xnnn
Table 13: Binary input signals in card location Xnnn
Name
Type
Description
Xnnn-Input m
1
BOOLEAN
Table 14: Binary output signals in card location Xnnn
Name
Type
Default
Description
Xnnn-Pmm
1
2
BOOLEAN
0=False
See the application
engineering guide for
terminal connections
1
Xnnn = Slot ID, for example, X100, X110, as applicable
2
Pmm = For example, PO1, PO2, SO1, SO2, as applicable
Basic functions
1MRS758755 C
46
REC615 & RER615
Technical Manual