![ABB Relion REC615 Technical Manual Download Page 447](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253447.webp)
4.4.5.7
Settings
PSPTUV Group settings
Table 469: PSPTUV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...1.200
xUn
0.001
0.500
Start value
Operate delay time 40...120000
ms
10
40
Operate delay time
Table 470: PSPTUV Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage block value 0.01...1.00
xUn
0.01
0.20
Internal blocking
level
Enable block value
0=False
1=True
1=True
Enable Internal
Blocking
Table 471: PSPTUV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 472: PSPTUV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Relative hysteresis
1.0...5.0
%
0.1
4.0
Relative hysteresis
for operation
4.4.5.8
Monitored data
PSPTUV Monitored data
Table 473: PSPTUV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
PSPTUV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
447