Parameter
Values (Range)
Unit
Step
Default
Description
-38=Recloser Y
(120)
-39=Recloser Z
(134)
Table 315: FEFLPTOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset
curve type
Table 316: FEFLPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
1
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 317: FEFLPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
287