![ABB Relion REC615 Technical Manual Download Page 231](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253231.webp)
Table 239: PHLPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
1
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 240: PHLPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
5=Wide P-to-P
2=DFT
Selects used meas-
urement mode
Table 241: PHHPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.10...40.00
xIn
0.01
0.10
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 40...200000
ms
10
40
Operate delay time
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
15=IEC Def. Time
Selection of time
delay curve type
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
231