![ABB Relion REC615 Technical Manual Download Page 588](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253588.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
5=off
A Hi high limit res
0.00...40.00
xIn
1
0.20
High alarm current
limit
A high limit res
0.00...40.00
xIn
1
0.05
High warning cur-
rent limit
A deadband res
100...100000
1
2500
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 603: RESCMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
2=DFT
Selects used meas-
urement mode
8.1.6.5
Monitored data
RESCMMXU Monitored data
Table 604: RESCMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
Io-A
FLOAT32
0.00...40.00
xIn
Measured residu-
al current
BLOCK
BOOLEAN
0=False
1=True
Block signal for
all binary out-
puts
HIGH_ALARM
BOOLEAN
0=False
1=True
High alarm
HIGH_WARN
BOOLEAN
0=False
1=True
High warning
I_INST_RES
FLOAT32
0.00...40.00
xIn
Residual current
Amplitude, mag-
nitude of instan-
taneous value
I_ANGL_RES
FLOAT32
-180.00...180.00
deg
Residual current
angle
I_DB_RES
FLOAT32
0.00...40.00
xIn
Residual current
Amplitude, mag-
nitude of repor-
ted value
I_DMD_RES
FLOAT32
0.00...40.00
xIn
Demand value of
residual current
Table continues on the next page
Measurement functions
1MRS758755 C
588
REC615 & RER615
Technical Manual