Table 544: SCEFRFLO Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
EF algorithm Sel
1=Load compensa-
tion
2=Load modelling
1=Load compensa-
tion
Selection for PhE-
loop calculation al-
gorithm
EF algorithm Cur
Sel
1=Io based
2=I2 based
1=Io based
Selection for earth-
fault current model
Load Com PP loops 0=Disabled
1=Enabled
1=Enabled
Enable load com-
pensation for
PP/3P-loops
Enable simple mod-
el
0=Disabled
1=Enabled
0=Disabled
Enable calc. with-
out impedance set-
tings for PP/3P-
loops
Distance estimate
Va
0.001...0.300
0.001
0.015
Allowed variation
of short circuit dis-
tance estimate
5.4.8
Monitored data
5.4.8.1
SCEFRFLO Monitored data
Table 545: SCEFRFLO Monitored data
Name
Type
Values (Range)
Unit
Description
RF
FLOAT32
0.0...1000000.0
ohm
Fault point re-
sistance in pri-
mary ohms
FAULT_LOOP
Enum
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-5=No fault
Fault impedance
loop
FLT_DISTANCE
FLOAT32
0.00...3000.00
pu
Fault distance in
units selected by
the user
FLT_DIST_Q
INT32
0...511
Fault distance
quality
RFLOOP
FLOAT32
0.0...1000000.0
ohm
Fault loop resist-
ance in primary
ohms
Table continues on the next page