![ABB Relion REC615 Technical Manual Download Page 586](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253586.webp)
Name
Type
Values (Range)
Unit
Description
4=low-low
U_INST_A
FLOAT32
0.00...5.00
xUn
UL1 Amplitude,
magnitude of in-
stantaneous val-
ue
U_ANGL_A
FLOAT32
-180.00...180.00
deg
UL1 angle
U_DMD_A
FLOAT32
0.00...5.00
xUn
Demand value of
UL1 voltage
U_INST_B
FLOAT32
0.00...5.00
xUn
UL2 Amplitude,
magnitude of in-
stantaneous val-
ue
U_ANGL_B
FLOAT32
-180.00...180.00
deg
UL2 angle
U_DMD_B
FLOAT32
0.00...5.00
xUn
Demand value of
UL2 voltage
U_INST_C
FLOAT32
0.00...5.00
xUn
UL3 Amplitude,
magnitude of in-
stantaneous val-
ue
U_ANGL_C
FLOAT32
-180.00...180.00
deg
UL3 angle
U_DMD_C
FLOAT32
0.00...5.00
xUn
Demand value of
UL3 voltage
8.1.5.6
Technical data
Table 598: VMMXU Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: f
n
±2
Hz
At voltages in range 0.01…1.15 × U
n
±0.5 % or ±0.002 × U
n
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
8.1.5.7
Technical revision history
Table 599: VMMXU Technical revision history
Technical revision
Change
B
Phase and phase-to-phase voltage angle val-
ues and demand values added to Monitored
data view.
C
Internal improvement.
D
Internal improvement.
Measurement functions
1MRS758755 C
586
REC615 & RER615
Technical Manual