![ABB Relion REC615 Technical Manual Download Page 567](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253567.webp)
Name
Type
Values (Range)
Unit
Description
opening opera-
tion
T_TRV_CL
FLOAT32
0...60000
ms
Travel time of
the CB dur-
ing closing oper-
ation
T_SPR_CHR
FLOAT32
0.00...99.99
s
The charging
time of the CB
spring
NO_OPR
INT32
0...99999
Number of CB
operation cycle
INA_DAYS
INT32
0...9999
The number of
days CB has
been inactive
CB_LIFE_A
INT32
-99999...99999
CB Remaining
life phase A
CB_LIFE_B
INT32
-99999...99999
CB Remaining
life phase B
CB_LIFE_C
INT32
-99999...99999
CB Remaining
life phase C
IPOW_A
FLOAT32
0.000...30000.00
0
Accumulated
currents power
(Iyt), phase A
IPOW_B
FLOAT32
0.000...30000.00
0
Accumulated
currents power
(Iyt), phase B
IPOW_C
FLOAT32
0.000...30000.00
0
Accumulated
currents power
(Iyt), phase C
SSCBR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
7.1.9
Technical data
Table 580: SSCBR Technical data
Characteristic
Value
Current measuring accuracy
±1.5 % or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0 %
Table continues on the next page
1MRS758755 C
Condition monitoring functions
REC615 & RER615
Technical Manual
567