![ABB Relion REC615 Technical Manual Download Page 474](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253474.webp)
4.7.6
Signals
Table 503: MAPGAPC Input signals
Name
Type
Default
Description
AI_VALUE
FLOAT32
0.0
Analogue input value
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
ENA_ADD
BOOLEAN
0=False
Enable start added
Table 504: MAPGAPC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.7.7
Settings
4.7.7.1
MAPGAPC Group settings
Table 505: MAPGAPC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
-10000.0...10000.0
0.1
0.0
Start value
Start value Add
-100.0...100.0
0.1
0.0
Start value Add
Operate delay time 0...200000
ms
100
0
Operate delay time
Table 506: MAPGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Over
2=Under
1=Over
Operation mode
Table 507: MAPGAPC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
100
0
Reset delay time
Absolute hysteresis 0.01...100.00
0.01
0.10
Absolute hysteresis
for operation
4.7.8
Monitored data
Protection functions
1MRS758755 C
474
REC615 & RER615