4.4.2.7
Signals
Table 442: PHPTUV Input signals
Name
Type
Default
Description
U_A_AB
SIGNAL
0
Phase to earth volt-
age A or phase to
phase voltage AB
U_B_BC
SIGNAL
0
Phase to earth volt-
age B or phase to
phase voltage BC
U_C_CA
SIGNAL
0
Phase to earth volt-
age C or phase to
phase voltage CA
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
Table 443: PHPTUV Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.4.2.8
Settings
PHPTUV Group settings
Table 444: PHPTUV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.05...1.20
xUn
0.01
0.90
Start value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 60...300000
ms
10
60
Operate delay time
Operating curve
type
5=ANSI Def. Time
15=IEC Def. Time
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
15=IEC Def. Time
Selection of time
delay curve type
Table 445: PHPTUV Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
2=Def time reset
1=Immediate
Selection of reset
curve type
Type of time reset
1=Freeze Op timer
2=Decrease Op tim-
er
1=Freeze Op timer
Selection of time
reset
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual