![ABB Relion REC615 Technical Manual Download Page 171](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253171.webp)
Table 192: CONTROL output signals
Name
Type
Description
OFF
BOOLEAN
Control output OFF
LOCAL
BOOLEAN
Control output Local
STATION
BOOLEAN
Control output Station
REMOTE
BOOLEAN
Control output Remote
ALL
BOOLEAN
Control output All
BEH_BLK
BOOLEAN
Logical device CTRL block
status
BEH_TST
BOOLEAN
Logical device CTRL test sta-
tus
3.17.11.9
Settings
Table 193: Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
LR control
1=LR key
2=Binary input
1=LR key
LR control through LR key or binary
input
Station authority
1=L,R
2=L,S,R
3=L,R,L+R
4=L,S,S+R,L+S,L
+S+R
1=L,R
Control command originator cate-
gory usage
Control mode
1=On
2=Blocked
5=Off
1=On
Enabling and disabling control
3.17.11.10
Monitored data
Table 194: Monitored data
Name
Type
Values (Range)
Unit
Description
Command
response
Enum
0=No commands
1=Select open
2=Select close
3=Operate open
4=Operate close
5=Direct open
6=Direct close
7=Cancel
8=Position reached
9=Position timeout
Latest command re-
sponse
Table continues on the next page
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
171