Parameter
Values (Range)
Unit
Step
Default
Description
Ng Seq V High limit 0.00...4.00
xUn
1
0.05
High warning volt-
age limit for nega-
tive sequence volt-
age
Ng Seq V low limit
0.00...4.00
xUn
1
0.00
Low warning volt-
age limit for nega-
tive sequence volt-
age
Ng Seq V low low
Lim
0.00...4.00
xUn
1
0.00
Low alarm voltage
limit for negative
sequence voltage
Ng Seq V deadband 100...100000
1
10000
Deadband configu-
ration value for
negative sequence
voltage for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Zro V Hi high Lim
0.00...4.00
xUn
1
0.20
High alarm voltage
limit for zero se-
quence voltage
Zro V High limit
0.00...4.00
xUn
1
0.05
High warning volt-
age limit for zero
sequence voltage
Zro V low limit
0.00...4.00
xUn
1
0.00
Low warning volt-
age limit for zero
sequence voltage
Zro V low low Lim
0.00...4.00
xUn
1
0.00
Low alarm voltage
limit for zero se-
quence voltage
Zro V deadband
100...100000
1
10000
Deadband configu-
ration value for
zero sequence volt-
age for integral cal-
culation. (percent-
age of difference
between min and
max as 0,001 % s)
8.1.10.5
Monitored data
VSMSQI Monitored data
Table 627: VSMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
NgSeq-kV
FLOAT32
0.00...4.00
xUn
Measured nega-
tive sequence
voltage
PsSeq-kV
FLOAT32
0.00...4.00
xUn
Measured posi-
tive sequence
voltage
ZroSeq-kV
FLOAT32
0.00...4.00
xUn
Measured zero
sequence volt-
age
U2_INST
FLOAT32
0.00...4.00
xUn
Negative se-
quence voltage
amplitude, in-
Table continues on the next page
Measurement functions
1MRS758755 C
600
REC615 & RER615