9.4.7
Signals
9.4.7.1
DARREC Input signals
Table 686: DARREC Input signals
Name
Type
Default
Description
INIT_1
BOOLEAN
0=False
AR initialization /
blocking signal 1
INIT_2
BOOLEAN
0=False
AR initialization /
blocking signal 2
INIT_3
BOOLEAN
0=False
AR initialization /
blocking signal 3
INIT_4
BOOLEAN
0=False
AR initialization /
blocking signal 4
INIT_5
BOOLEAN
0=False
AR initialization /
blocking signal 5
INIT_6
BOOLEAN
0=False
AR initialization /
blocking signal 6
DEL_INIT_2
BOOLEAN
0=False
Delayed AR initializa-
tion / blocking signal
2
DEL_INIT_3
BOOLEAN
0=False
Delayed AR initializa-
tion / blocking signal
3
DEL_INIT_4
BOOLEAN
0=False
Delayed AR initializa-
tion / blocking signal
4
BLK_RECL_T
BOOLEAN
0=False
Blocks and resets re-
close time
BLK_RCLM_T
BOOLEAN
0=False
Blocks and resets re-
claim time
BLK_THERM
BOOLEAN
0=False
Blocks and holds the
reclose shot from the
thermal overload
CB_POS
BOOLEAN
0=False
Circuit breaker posi-
tion input
CB_READY
BOOLEAN
1=True
Circuit breaker status
signal
INC_SHOTP
BOOLEAN
0=False
A zone sequence co-
ordination signal
INHIBIT_RECL
BOOLEAN
0=False
Interrupts and in-
hibits reclosing se-
quence
Table continues on the next page
1MRS758755 C
Control functions
REC615 & RER615
Technical Manual
683