Table 69: RESTVTR Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm
WARNING
BOOLEAN
Warning
3.14.4.5
Settings
Table 70: RESTVTR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Primary voltage
0.100...440.000
kV
0.001
11.547
Primary voltage
Secondary voltage
60...210
V
1
100
Secondary voltage
Amplitude Corr
0.9000...1.1000
0.0001
1.0000
Amplitude correc-
tion
Angle correction
-20.0000...20.0000
deg
0.0001
0.0000
Angle correction
factor
3.14.4.6
Monitored data
Monitored data is available in three locations.
• Monitoring > I/O status > Analog inputs
• Monitoring > IED status > SMV traffic
• Monitoring > IED status > SMV accuracy
3.15
GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32 data
types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by
bad data quality bits or GOOSE communication failure. See IEC 61850 engineering
guide for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
Settings
3.15.1
GOOSERCV_BIN function block
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
119