9.5.5
Application
Figure 353: Application configuration example
A recommended application configuration example is described in
Undervoltage detection on bus 1 and undervoltage detection on bus 2 are
connected directly to the
UN_U_BUS1
and
UN_U_BUS2
. The undervoltage indication
at each bus can be detected from for example functions PHPTUV, VMMXU or
PHSVPR.
Load fault detections on busbar, such as overcurrent and earth-fault functions are
connected as grouped protection input to
BLOCK
.
Auto mode OFF/ON is connected
to input
BLOCK
.
Control functions
1MRS758755 C
696
REC615 & RER615
Technical Manual