Table 328: EFIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
4.2.1.10
Monitored data
Table 329: FEFLPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
FEFLPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 330: EFLPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
EFLPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 331: EFHPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
EFHPTOC
Enum
1=on
2=blocked
3=test
Status
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
291