![ABB Relion REC615 Technical Manual Download Page 625](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253625.webp)
Parameter
Values
(Range)
Unit
Step
Default
Description
3=Both
4=Level trig-
ger off
Storage mode 0=Waveform
1=Trend / cy-
cle
1
0
Storage mode
for the binary
channel
Channel id
text
0 to 64 char-
acters, alpha-
numeric
DR binary
channel X
Identification
text for the
analog chan-
nel used in
the COM-
TRADE format
Table 644: RDRE Control data
Parameter
Values
(Range)
Unit
Step
Default
Description
Trig recording 0=Cancel
1=Trig
Trigger the
disturbance
recording
Clear record-
ings
0=Cancel
1=Trig
Clear all re-
cordings cur-
rently in
memory
8.2.6
Monitored data
8.2.6.1
Monitored data
Table 645: RDRE Monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Number of record-
ings
0...100
Number of record-
ings currently in
memory
Rem. amount of
rec.
0...100
Remaining amount
of recordings that
fit into the availa-
ble recording mem-
ory, when current
settings are used
Rec. memory used
0...100
%
Storage mode for
the binary channel
Time to trigger
0...604 800
s
Time remaining to
the next periodic
triggering
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
625