Parameter
Values (Range)
Unit
Step
Default
Description
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 417: NSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
4.3.1.8
Monitored data
NSPTOC Monitored data
Table 418: NSPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
NSPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.3.1.9
Technical data
Table 419: NSPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±1.5% of the set value or ±0.002 × I
n
Start time
1
2
Minimum
Typical
Maximum
I
Fault
= 2 × set
Start value
I
Fault
= 10 × set
Start value
23 ms
15 ms
26 ms
18 ms
28 ms
20 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Table continues on the next page
1
Negative sequence current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution
of 1000 measurements
2
Includes the delay of the signal output contact
Protection functions
1MRS758755 C
414
REC615 & RER615
Technical Manual