Table 514: INRPHAR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
5.1.8
Monitored data
5.1.8.1
INRPHAR Monitored data
Table 515: INRPHAR Monitored data
Name
Type
Values (Range)
Unit
Description
INRPHAR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.1.9
Technical data
Table 516: INRPHAR Technical data
Characteristic
Value
Operation accuracy
At the frequency f = f
n
Current measurement:
±1.5 % of the set value or ±0.002 × I
n
Ratio I2f/I1f measurement:
±5.0 % of the set value
Reset time
+35 ms / -0 ms
Reset ratio
Typically 0.96
Operate time accuracy
+35 ms / -0 ms
5.1.10
Technical revision history
Table 517: INRPHAR Technical revision history
Technical revision
Change
B
Internal improvement
C
Internal improvement
Protection related functions
1MRS758755 C
480
REC615 & RER615
Technical Manual