Parameter
Values (Range)
Unit
Step
Default
Description
-21=Recloser C
-22=Recloser D
-23=Recloser E
-24=Recloser F
-25=Recloser G
-26=Recloser H
-27=Recloser J
-28=Recloser Kg
-29=Recloser Kp
-30=Recloser L
-31=Recloser M
-32=Recloser N
-33=Recloser P
-34=Recloser R
-35=Recloser T
-36=Recloser V
-37=Recloser W
-38=Recloser Y
-39=Recloser Z
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve
type
Table 235: FPHLPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
1
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Table continues on the next page
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual