8.1.12.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single-phase power and energy
measurement
SPEMMXU
SP, SE
SP, SE
8.1.12.2
Function block
Figure 302: Function block
8.1.12.3
Signals
Table 635: SPEMMXU Input signals
Name
Type
Default
Description
RSTACM
BOOLEAN
0=False
Reset of accumulated
energy reading
8.1.12.4
Settings
Table 636: SPEMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Power unit Mult
3=k
6=M
3=k
Unit multiplier for
presentation of the
power related val-
ues
Energy unit Mult
3=k
6=M
3=k
Unit multiplier for
presentation of the
energy related val-
ues
Active power Dir
1=Forward
2=Reverse
1=Forward
Direction of active
power flow: For-
ward, Reverse
Reactive power Dir 1=Forward
2=Reverse
1=Forward
Direction of reac-
tive power flow:
Forward, Reverse
Table 637: SPEMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Forward Wh Initial
0...999999999
1
0
Preset Initial value
for forward active
energy
Reverse Wh Initial
0...999999999
1
0
Preset Initial value
for reverse active
energy
Table continues on the next page
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
607