Parameter
Values (Range)
Unit
Step
Default
Description
Allow Non Dir
0=False
1=True
0=False
Allows prot activation as
non-dir when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measure-
ment mode
Min operate cur-
rent
0.01...1.00
xIn
0.01
0.01
Minimum operating cur-
rent
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating volt-
age
4.1.2.10
Monitored data
Table 281: FDPHLPDOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault
direction
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction infor-
mation
DIR_A
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase
A
DIR_B
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase
B
DIR_C
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase
C
Table continues on the next page
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
261