Disabled
Quantity not selected
U23
Phase-to-phase 23 voltage
U31
Phase-to-phase 31 voltage
UL1
Phase-to-earth 1 voltage
UL2
Phase-to-earth 2 voltage
UL3
Phase-to-earth 3 voltage
U12B
Phase-to-phase 12 voltage, B side
U23B
Phase-to-phase 23 voltage, B side
U31B
Phase-to-phase 31 voltage, B side
UL1B
Phase-to-earth 1 voltage, B side
UL2B
Phase-to-earth 2 voltage, B side
UL3B
Phase-to-earth 3 voltage, B side
S
Apparent power
P
Real power
Q
Reactive power
PF
Power factor
If the data source for the selected quantity is removed, for example, with
Application Configuration in PCM600, the load profile recorder stops
recording it and the previously collected data are cleared.
3.19.2.2
Length of record
The recording capability is about 7.4 years when one quantity is recorded and
the demand interval is set to 180 minutes. The recording time scales down
proportionally when a shorter demand time is selected or more quantities are
recorded. The recording lengths in days with different settings used are presented
. When the recording buffer is fully occupied, the oldest data are
overwritten by the newest data.
Table 212: Recording capability in days with different settings
Demand interval
1
5
10
15
30
60
180
Table continues on the next page
Basic functions
1MRS758755 C
192
REC615 & RER615
Technical Manual