4.2.2.11
Settings
Table 352: DEFLPDEF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...5.000
xIn
0.005
0.010
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time
Selection of time
delay curve type
Operate delay time 50...200000
ms
10
50
Operate delay time
Characteristic an-
gle
-179...180
deg
1
-90
Characteristic an-
gle
Max forward angle
0...180
deg
1
80
Maximum phase
angle in forward di-
rection
Max reverse angle
0...180
deg
1
80
Maximum phase
angle in reverse di-
rection
Min forward angle
0...180
deg
1
80
Minimum phase an-
gle in forward di-
rection
Min reverse angle
0...180
deg
1
80
Minimum phase an-
gle in reverse direc-
tion
Voltage start value 0.010...1.000
xUn
0.001
0.010
Voltage start value
Table 353: DEFLPDEF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
2=Def time reset
1=Immediate
Selection of reset
curve type
Table continues on the next page
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual