Parameter
Values (Range)
Unit
Step
Default
Description
Frq Op counter lim-
it
0...250
1
0
Frequent operation
counter lockout
limit
Frq Op counter
time
1...250
min
1
1
Frequent operation
counter time
Frq Op recovery
time
1...250
min
1
1
Frequent operation
counter recovery
time
Auto init
0...63
1
0
Defines INIT lines
that are activated
at auto initiation
Table 689: DARREC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Manual close mode 0=False
1=True
0=False
Manual close mode
Wait close time
50...10000
ms
50
250
Allowed CB closing
time after reclose
command
Max wait time
100...1800000
ms
100
10000
Maximum wait time
for BLK_RECL_T re-
lease
Max trip time
100...10000
ms
100
10000
Maximum wait time
for deactivation of
protection signals
Max Thm block
time
100...1800000
ms
100
10000
Maximum wait time
for thermal block-
ing signal deactiva-
tion
Cut-out time
0...1800000
ms
100
10000
Cutout time for
protection coordi-
nation
Dsr time shot 1
0...10000
ms
100
0
Discrimination time
for first reclosing
Dsr time shot 2
0...10000
ms
100
0
Discrimination time
for second reclos-
ing
Dsr time shot 3
0...10000
ms
100
0
Discrimination time
for third reclosing
Dsr time shot 4
0...10000
ms
100
0
Discrimination time
for fourth reclosing
Auto wait time
0...60000
ms
10
2000
Wait time for re-
closing condition
fullfilling
Auto lockout reset
0=False
1=True
1=True
Automatic lockout
reset
Protection crd limit 1...5
1
1
Protection coordi-
nation shot limit
Protection crd
mode
1=No condition
2=AR inoperative
3=CB close manual
4=AR inop, CB man
5=Always
4=AR inop, CB man Protection coordi-
nation mode
Control line
0...63
1
63
Control line, de-
fines INIT inputs
which are protec-
tion signals
Enable shot jump
0=False
1=True
Enable shot jump-
ing
Table continues on the next page
Control functions
1MRS758755 C
686
REC615 & RER615
Technical Manual