Figure 326: Functional module diagram
9.4.4.1
Signal collection and delay logic
When the protection trips, the initiation of autoreclosing shots is in most
applications executed with the
INIT_1...6
inputs. The
DEL_INIT2...4
inputs are
not used. In some countries, starting the protection stage is also used for the shot
initiation. This is the only time when the
DEL_INIT
inputs are used.
1MRS758755 C
Control functions
REC615 & RER615
Technical Manual
659