PDNSPTOC Group settings
Table 423: PDNSPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
10...100
%
1
10
Start value
Operate delay time 100...30000
ms
1
100
Operate delay time
Table 424: PDNSPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 425: PDNSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Min phase current
0.05...0.30
xIn
0.01
0.10
Minimum phase
current
4.3.2.8
Monitored data
PDNSPTOC Monitored data
Table 426: PDNSPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
RATIO_I2_I1
FLOAT32
0.00...999.99
%
Measured cur-
rent ratio I2 / I1
PDNSPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.3.2.9
Technical data
Table 427: PDNSPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2
Hz
±2% of the set value
Start time
<70 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Table continues on the next page
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
419