![ABB Relion REC615 Technical Manual Download Page 50](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253050.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
COT Length
1...2
1
1
Cause of transmission length
IOA Length
1...3
1
2
Information Object Address length
Link Address
Length
1...2
1
1
Link Address Length
ASDU Address
Length
1...2
1
1
ASDU Address Length
Single Char Resp
0=False
1=True
0=False
Single character response enabled/ disa-
bled
Show Bad Time
0=False
1=True
1=True
Enable/disable bad time quality indica-
tion in events
Time Format
0=Short 24bit
1=Full 56bit
1=Full 56bit
Time stamp format 3 or 7 octet
Event Time
0=Local
1=UTC
1=UTC
Selects between UTC/Local time
Overflow Mode
0=indication
1=Keep newest
0=in-
dication
Event buffer overflow handling mecha-
nism
OvInd IOA
0...16777215
1
60000
Overflow indication address for interro-
gated data
OvInd NoGI IOA
0...16777215
1
60000
Overflow indication address for non- in-
terrogated data
Event Order
0=Accurate time
1=Preserve chronology
0=Accurate
time
Selects the event ordering principle
Selection Timeout 1...65
s
1
30
Selection timeout for control SBO opera-
tions
Counter Reporting 0=Read by master
1=Spontaneous
0=Read by
master
Counter reporting after freeze
Freeze mode
0=Not in use t
1=Freeze only
2=Freeze and Reset
0=Not in use
Periodic freezing mode for integrated to-
tals
TX window (k)
1...20
1
12
IEC60870-5-104 transmit window (k)
RX window (w)
1...20
1
8
IEC60870-5-104 receive window (w)
TX timeout (t1)
1...60000
ms
1
30000
IEC60870-5-104 transmit timeout (t1)
RX timeout (t2)
1...60000
ms
1
10000
IEC60870-5-104 receive timeout (t1)
Test interval (t3)
1...60000
ms
1
20000
IEC60870-5-104 link test interval (t3)
Cyclical Period
1...604800
1
10
Cyclical period in seconds
IT_FRZ
0=False
1=True
0=False
Control point for freezing integrated to-
tals
Inverted DIR bit
0=False
1=True
0=False
Special mode for masters that require in-
verted DIR bit on Balanced IEC101 line.
If enabled, this protocol instance will be
non-compliant with the IEC 60870-5-101
standard.
Basic functions
1MRS758755 C
50
REC615 & RER615