Name
Type
Default
Description
U_B_BC
SIGNAL
0
Phase to earth volt-
age B or phase to
phase voltage BC
U_C_CA
SIGNAL
0
Phase to earth volt-
age C or phase to
phase voltage CA
Uo
SIGNAL
0
Residual voltage
U
1
SIGNAL
0
Positive phase se-
quence voltage
U
2
SIGNAL
0
Negative phase se-
quence voltage
BLOCK
BOOLEAN
0=False
Signal for blocking
the triggering
TRIGG
BOOLEAN
0=False
Distance calculation
triggering signal
TRIGG_XC0F
BOOLEAN
0=False
XC0F calculation trig-
gering signal
5.4.6.2
SCEFRFLO Output signals
Table 540: SCEFRFLO Output signals
Name
Type
Description
ALARM
BOOLEAN
Fault location alarm signal
5.4.7
Settings
5.4.7.1
SCEFRFLO Group settings
Table 541: SCEFRFLO Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Z Max phase load
1.0...10000.0
ohm
0.1
80.0
Impedance per
phase of max.
load, overcurr./un-
der-imp., PSL
Ph leakage Ris
20...1000000
ohm
1
210000
Line PhE leakage
resistance in pri-
mary ohms
Ph capacitive React 10...1000000
ohm
1
7000
Line PhE capaci-
tive reactance in
primary ohms
R1 line section A
0.000...1000.000
ohm / pu
0.001
1.000
Positive sequence
line resistance, line
section A
X1 line section A
0.000...1000.000
ohm / pu
0.001
1.000
Positive sequence
line reactance, line
section A
Table continues on the next page
1MRS758755 C
Protection related functions
REC615 & RER615
Technical Manual
517