Operating curve type
(F)DEFLPDEF
DEFHPDEF
(-25)=Recloser G (121)
x
(-26)=Recloser H (122)
x
(-27)=Recloser J (164)
x
(-28)=Recloser Kg (165)
x
(-29)=Recloser Kp (162)
x
(-30)=Recloser L (107)
x
(-31)=Recloser M (118)
x
(-32)=Recloser N (104)
x
(-33)=Recloser P (115)
x
(-34)=Recloser R (105)
x
(-35)=Recloser T (161)
x
(-36)=Recloser V (137)
x
(-37)=Recloser W (138)
x
(-38)=Recloser Y (120)
x
(-39)=Recloser Z (134)
x
For a detailed description of the timers, see
Table 343: Reset time characteristics supported by different stages
Reset curve type
(F)DEFLPDEF
DEFHPDEF
Note
(1) Immediate
x
x
Available for all operate time curves
(2) Def time reset
x
x
Available for all operate time curves
(3) Inverse reset
x
x
Available only for ANSI and user pro-
grammable curves
4.2.2.8
Directional earth-fault characteristics
Phase angle characteristic
The operation criterion phase angle is selected with the
Operation mode setting
using the value "Phase angle".
When the phase angle criterion is used, the function indicates with the
DIRECTION
output whether the operating quantity is within the forward or reverse operation
sector or within the non-directional sector.