CB2_POSOPEN
BOOLEAN
0=False
Circuit breaker open sta-
tus for bus 2
CB2_POSCLOSE
BOOLEAN
0=False
Circuit breaker close sta-
tus for bus 2
Table 696: ATSABTC Output signals
Name
Type
Description
OPEN_CB1
BOOLEAN
Circuit breaker open command for bus 1
CLOSE_CB1
BOOLEAN
Circuit breaker close command for bus 1
OPEN_CB2
BOOLEAN
Circuit breaker open command for bus 2
CLOSE_CB2
BOOLEAN
Circuit breaker close command for bus 2
INPRO
BOOLEAN
Automatic operation in progress
BLKD_AL
BOOLEAN
Automatic transfer switch blocked alarm
9.5.7
Settings
Table 697: ATSABTC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Main bus priority
1=Bus 1
2=Bus 2
1=Bus 1
Main bus priority (1 or 2)
Operate delay CB tr 0...120000
ms
10
200
Circuit breaker trip delay
Transfer dead time 0...120000
ms
10
100
Transfer dead time for closing of
circuit breaker
Reconnection delay 0...300000
ms
10
60000
Delay for opening of non prioritized
CB
9.5.8
Monitored data
Table 698: ATSABTC Monitored data
Name
Type
Values (Range)
Unit
Description
ATSABTC
Enum
1=on
2=blocked
3=test
Status
Control functions
1MRS758755 C
698
REC615 & RER615
Technical Manual