When the IDMT operate time curve is selected, the functionality of the Timer in the
drop-off state depends on the combination of the
Type of reset curve, Type of time
reset and Reset delay time settings.
Table 440: Reset time functionality when IDMT operation time curve selected
Reset functionality
Setting Type of
reset curve
Setting Type of
time reset
Setting Reset
delay time
Instantaneous
reset
Operation timer
is “Reset instan-
taneously” when
drop-off occurs
“Immediate”
Setting has no
effect
Setting has no
effect
Frozen timer
Operation timer
is frozen during
drop-off
“Def time reset”
“Freeze Op tim-
er”
Operate timer is
reset after the
set
Reset delay
time
has elapsed
Linear decrease
Operation timer
value linearly de-
creases during
the drop-off sit-
uation
“Def time reset”
“Decrease Op
timer”
Operate timer is
reset after the
set
Reset delay
time
has elapsed
Protection functions
1MRS758755 C
430
REC615 & RER615
Technical Manual