Name
Type
Values (Range)
Unit
Description
Q_DB
FLOAT32
-999999.9...9999
99.9
kVAr
Reactive power,
magnitude of re-
ported value
Q_DMD
FLOAT32
-999999.9...9999
99.9
kVAr
Demand value of
reactive power
PF_INST
FLOAT32
-1.00...1.00
Power factor,
magnitude of in-
stantaneous val-
ue
PF_DB
FLOAT32
-1.00...1.00
Power factor,
magnitude of re-
ported value
PF_DMD
FLOAT32
-1.00...1.00
Demand value of
power factor
EA_RV_ACM
INT64
0...999999999
kWh
Accumulated re-
verse active en-
ergy value
ER_RV_ACM
INT64
0...999999999
kVArh
Accumulated re-
verse reactive
energy value
EA_FWD_ACM
INT64
0...999999999
kWh
Accumulated for-
ward active ener-
gy value
ER_FWD_ACM
INT64
0...999999999
kVArh
Accumulated for-
ward reactive en-
ergy value
Max demand S
FLOAT32
-999999.9...9999
99.9
kVA
Maximum de-
mand value of
apparent power
Min demand S
FLOAT32
-999999.9...9999
99.9
kVA
Minimum de-
mand value of
apparent power
Max demand P
FLOAT32
-999999.9...9999
99.9
kW
Maximum de-
mand value of
active power
Min demand P
FLOAT32
-999999.9...9999
99.9
kW
Minimum de-
mand value of
active power
Max demand Q
FLOAT32
-999999.9...9999
99.9
kVAr
Maximum de-
mand value of re-
active power
Min demand Q
FLOAT32
-999999.9...9999
99.9
kVAr
Minimum de-
mand value of re-
active power
Time max dmd S Timestamp
Time of maxi-
mum demand
Table continues on the next page
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
605