Parameters 197
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Supervision 1
(see page
).
21
Supervision 2
Bit 1 of
(see page
22
Supervision 3
Bit 2 of
(see page
23
on
-
Defines a deadband around the setpoint.
Whenever process feedback enters the
deadband, a delay timer starts. If the feedback
remains within the deadband longer than the
delay (
), the PID
controller output is frozen. Normal operation
resumes after the feedback value leaves the
deadband.
0.00
0.00……
200000.00
Deadband range.
1 = 1
Delay for the deadband. See parameter
.
0.0 s
0.0 … 3600.0 s
Delay for deadband area.
1 = 1 s
No.
Name/Value
Description
Def/
FbEq16
Setpoint
Time
Feedback
PID controller
output
PID controller
output frozen